Line Failure Localization of Power Networks Part II: Cut Set Outages

Abstract

Transmission line failure in power systems prop-agate non-locally, making the control of the resulting outages extremely difficult. In Part II of this paper, we continue the study of line failure localizability in transmission networks and characterize the impact of cut set outages. We establish a Simple Path Criterion, showing that the propagation pattern due to bridge outages, a special case of cut set failures, are fully determined by the positions in the network of the buses that participate in load balancing. We then extend our results to general cut set outages. In contrast to non-cut outages discussed in Part I whose subsequent line failures are contained within the original blocks, cut set outages typically impact the whole network, affecting the power flows on all remaining lines. We corroborate our analytical results in both parts using the IEEE 118-bus test system, in which the failure propagation patterns exhibit a clear block-diagonal structure predicted by our theory, even when using full AC power flow equations.

Additional Information

© 2021 IEEE. This work is licensed under a Creative Commons Attribution 4.0 License. Manuscript received May 27, 2020; revised November 1, 2020 and January 19, 2021; accepted March 1, 2021. Date of publication April 13, 2021; date of current version August 19, 2021. This work was supported by Resnick Fellowship, Linde Institute Research Award, NWO Rubicon under Grant 680.50.1529, and by NSF under Grants CCF 1637598, ECCS 1619352, ECCS 1931662, CNS 1545096, CNS 1518941, CPS ECCS 1739355, and CPS 154471. Paper no. TPWRS-00762-2020.

Attached Files

Published - Line_Failure_Localization_of_Power_Networks_Part_II_Cut_Set_Outages.pdf

Submitted - 2005.11320.pdf

Files

Line_Failure_Localization_of_Power_Networks_Part_II_Cut_Set_Outages.pdf
Files (2.5 MB)
Name Size Download all
md5:30e694527351ad9081d209dcb117cffb
2.0 MB Preview Download
md5:898a3403f1c353d18e3e3ba6dbb398a5
506.4 kB Preview Download

Additional details

Created:
August 20, 2023
Modified:
October 20, 2023